8.2.

COOLING OPERATION

8.2.1.
Room Temperature Control
1. When the remote control setting temperature is less than 24°C.
2. When the remote control setting temperature is 24°C and above.
∙ Compressor OFF temperature = Compressor ON temperature.
∙ The operation frequency can be changed every 30 seconds.
∙ 30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
∙ The compressor stops when the intake air temperature reaches 1°C below internal setting temperature and continues for 3
minutes.
∙ When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
∙ When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
∙ When the compressor stops, the outdoor fan motor stops 30 seconds later.