CS-VG120KE / CU-VG120KE
Deice Operation Time Chart
∙ Compressor frequency is set at 73Hz when the deice operation starting signal is generated.
∙ 150 seconds later deice operation starting signal is generated, indoor fan, outdoor fan, 4-way valve are turned off and
compressor operates at 95Hz for 30 seconds. (Deice operation starts)
∙ During deice operation, the compressor operating frequency is set at 103Hz.
∙ Deice will end when the outdoor heat exchanger temperature rises to 16°C or after 11 minutes.