Figure 3-35 Cable routes
(1) Ports for indoor
and outdoor units
signal cables
3.12 Leakage Test with Nitrogen
Context
● The leakage test with nitrogen described in this section is dedicated for testing
the leaks of the indoor unit and the pipes connected to it.
● The measuring range of the pressure gauge must be greater than or equal to
4.0 MPa, and the tolerance range of the leather hose must be greater than or
equal to 4.5 MPa.
● During the pressure preservation process, do not remove the leather hose and
pressure gauge; otherwise, nitrogen may leak.
Procedure
Step 1 Open the stop valves for the gas pipe and liquid pipe of the indoor unit.
Before opening the indoor unit stop valves, ensure that the stop valves for the gas
pipe and liquid pipe of the outdoor unit are closed.
Issue 02 (2020-11-09)
(2) Ports for teamwork
and monitoring cables
NO TICE
NO TICE
Copyright © Huawei Technologies Co., Ltd.
(3) Ports for indoor
(4) Ports for outdoor
unit power cable
unit power cable
3 Installation Guide