Huawei NetCol8000-A013 User Manual page 179

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Menu
Setting > Admin Menu
> System Setting >
Outdoor Fan
Setting > Admin Menu
> System Setting > EEV
Issue 02 (2020-11-09)
Name
Dehumid Speed
Min S/R Air Temp Diff
Max S/R Air Temp
Diff
Start Delay
Stop Delay
Min Speed
Max Speed
Min Run Pressure
Start Pressure
Max Run Pressure
Min Open
Max Open
Standby Open
Suct Super Heat Set
point
Suct Super Heat Dead
zone
Adjust Cycle
P-band
Integral Time
Constant
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
80%
Minimum value:
(Maximum
speed of the
indoor fan –
30%) or
minimum speed
of the indoor
fan, take the
smaller value
Maximum value:
maximum speed
of the indoor fan
5.0°C
1.0°C to 20.0°C
10.0°C
1.0°C to 20.0°C
30s
0 to 99s
30s
0 to 99s
27.5%
20% to 40%
100%
40% to 100%
2.10 MPa
1.0 MPa to 3.5
MPa
2.26 MPa
1.0 MPa to 3.5
MPa
2.80 MPa
2.5 MPa to 4.0
MPa
52 step
0 to 480 step
480 step
0 to 480 step
300 step
Min Open to
Max Open
6.0°C
2.0°C to 20.0°C
2.0°C
0 to 5.0°C
10s
5s to 300s
2.0
0.1 to 10.0
60s
1s to 999s