Preventive Maintenance Tables - Huawei NetCol8000-A013 User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)

5.1.2 Preventive Maintenance Tables

Monthly Preventive Maintenance Table
Table 5-1 Monthly Preventive Maintenance Table
Maintenance Item
Return air filter
Wet film humidifier
Refrigerant pipe and
water pipe
Issue 02 (2020-11-09)
maintenance. If you need to perform maintenance tasks such as measuring
the current, voltage, and temperature when the equipment is operating,
connect the power supply only after you have finished all equipment
connections. Disconnect the power supply when you finish maintenance.
Take protective measures during electrical maintenance, such as wearing
insulation gloves and shoes.
Exercise caution when performing professional maintenance tasks. For details,
consult Huawei technical support.
During component replacement, do not lean any material against the cabinet.
Expected Result
Check that the return air filter is
clean and not blocked.
Check that the return air filter is not
damaged or distorted.
Check that the valve on the water
inlet pipe is open.
Check that the wet film is clean and
have no scale.
Check that no operating overtime
alarm is generated for the
humidifier.
Check that the refrigerant pipe is
free of oil stains and rust.
Check that the water pipe is
tightened and free of water leakage.
The thermal insulation foam is
intact.
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
Troubleshooting
Clean the air filter with water
(recommended).
If it is damaged, replace the air
filter.
Open the valve on the water inlet
pipe.
If there is much water scale,
replace the wet film humidifier.
Replace the wet film humidifier.
Check for leakage and repair the
pipe.
Check for leakage and repair the
pipe, or reconnect the pipe.
Wrap the thermal insulation foam
again.
78

Advertisement

Table of Contents
loading

Table of Contents