Huawei NetCol8000-A013 User Manual page 175

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Menu
Setting > User Menu >
Temp&Humid Setting
Setting > User Menu >
Comm Setting
Setting > User Menu >
Password Setting
Setting > Admin Menu
> Alarm Setting >
Temp&Humid Sensor
Setting > Admin Menu
> Alarm Setting >
Compressor
Issue 02 (2020-11-09)
Name
Temp for HT Start All
Low Temp Start All
Temp for LT Start All
Return Air Temp Set
Return Air Humid Set
Baud Rate
Comm Address
Enable Monitoring
Resistor
/
Return Air HT Alarm
Return Air HT Thres
Return Air LT Alarm
Return Air LT Thres
High Humid Alarm
High Humid Thres
Low Humid Alarm
Low Humid Thres
Temp&Humid Alarm
Delay
Run Time out Alarm
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
Hide or
24.0°C to 35.0°C
31
Hide or
Enable/Disable
Disable
Hide or
10.0°C to 18.0°C
13
24.0
The minimum
temperature
setting to the
maximum
temperature
setting
50.0
The minimum
humidity setting
to the maximum
humidity setting
9600
9600/19200
Setting
1 to 255
No
Yes/No
000001
Six-digit number
Enable
Enable/Disable
32.0°C
25°C to 40.0°C
Enable
Enable/Disable
12.0°C
5°C to 24.0°C
Enable
Enable/Disable
85.0%
65.0% RH to
RH
95.0% RH
Enable
Enable/Disable
10.0%
5.0% RH to
RH
35.0% RH
60s
5s to 999s
Enable
Enable/Disable
168