Huawei NetCol8000-A013 User Manual page 95

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Alarm
Alarm Name
ID
207
Comp LP Switch
Alarm
208
Comp LP Switch
Lock Alarm
Issue 02 (2020-11-09)
System
Possible Causes
Action
The
1. The condenser fins
compressor
shuts down.
2. The indoor fan or its
3. The cables to the
4. The low pressure
5. Refrigerant leaks.
6. The indoor unit is
7. The EEV is faulty.
8. The stop valve is
9. The filter is dirty or
10.The selected model
11.The connecting pipe
The
The Comp LP Switch
compressor
Alarm is triggered
shuts down.
multiple times within a
(The alarm
specified period of
needs to be
time.
manually
cleared.)
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
are dirty or blocked.
drive is faulty.
low pressure switch
are loose or
damaged.
switch is faulty.
not properly
installed.
not fully open.
blocked.
is incorrect.
is bent.
Solution
1. Clean the condenser
fins.
2. Maintain or replace
the indoor fan drive
or indoor fan.
3. Check the cable
connections to the
low pressure switch.
4. Maintain or replace
the low pressure
switch.
5. Identify and repair
the leaking points,
and refill refrigerant
after maintenance.
6. Reinstall the indoor
unit.
7. Maintain or replace
the EEV coil or EEV.
8. Check and fully
open the stop valve.
9. Check and replace
the filter.
10.Check that the
selected model is
correct.
11.Check and replace
the connecting pipe.
Refer to the solution to
the Comp LP Switch
Alarm.
88