Setting
Item
Active
Units in
Group
Rotation
Function
Rotation
Type
Rotation
Cycle
Rotation
Time
High
Temp
Start All
Temp for
HT Start
All
Issue 02 (2020-11-09)
Description
Indicates the
number of running
units in a group. The
value is an integer
ranging from 1 to
the number of units
in a group.
Indicates whether to
disable or enable
the active and
standby smart
cooling products to
work alternatively to
maximize their
service life.
Can be set to
Address or hour
Indicates the interval
between rotations.
The value ranges
from 1 to 30.
Indicates the time
when rotation takes
place. The value can
be any hour in a day
(0–23).
When it is enabled,
if the return air
temperature is
higher than Temp
for HT Start All, all
the smart cooling
products in a group
will start cooling
simultaneously.
-
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Principle
Assign the address 1
to the master unit,
and assign addresses
starting from 2
consecutively to all
running units in a
group. Remaining
units will be
regarded as standby
units.
It is recommended
that the function be
enabled when the
load power is even.
You are advised not
to change the value.
/
/
You are advised not
to change the value.
You are advised not
to change the value.
Default Value
2
Disable
Address
1D
00:00
Disable
31°C
71