Alarm
Alarm Name
ID
803
Return Air High
Humid Alarm
804
Return Air Low
Humid Alarm
805
Smoke Sensor
Alarm
Issue 02 (2020-11-09)
System
Possible Causes
Action
--
1. The wet load is
2. The
3. The return air high
4. The humidity
--
1. The unit is a
2. The humidification
3. The return air low
4. The humidity
Turn off all
1. There is smoke.
2. Cables to the smoke
3. The smoke sensor is
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
large.
dehumidification
function is not
started.
humidity alarm
threshold is
inappropriate for
the working
conditions.
displayed by the
humidity sensor is
different from the
actual humidity.
cooling-only unit.
function is not
started.
humidity alarm
threshold is
inappropriate for
the working
conditions.
displayed by the
humidity sensor is
different from the
actual humidity.
sensor are not
properly connected.
faulty.
Solution
1. Add smart cooling
products.
2. Start the
dehumidification
function.
3. Adjust the return air
high humidity alarm
threshold.
4. Calibrate or replace
the humidity sensor.
1. Replace the unit
with one that has
heating and
humidification
functions.
2. Start the
humidification
function.
3. Adjust the return air
low humidity alarm
threshold.
4. Calibrate or replace
the humidity sensor.
1. Clear smoke from
the equipment
room and reset the
smoke sensor.
2. Check the cables to
the smoke sensor.
3. Maintain or replace
the smoke sensor.