NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Menu
Setting > Admin Menu
> System Setting >
Indoor Fan
Issue 02 (2020-11-09)
Name
Min Speed
Max Speed
Oil Return Cycle
Forced Oil Return
Cycle
Oil Return Speed
Stop Vacuum Speed
Stop Vacuum Pressure 0.48 MPa
Comp Preheating
Dis HT Rise Limit
Temp
Dis HT Drop Temp
Min Speed
Max Speed
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
1200
1200 rpm to
rpm
4800 rpm
4800
1200 rpm to
rpm
4800 rpm
180s
120s to 600s
2h
2h to 24h
3000rpm
From Min Speed
to Max Speed
1800
From Min Speed
rpm
to Max Speed
0 to 1.5 MPa
On (The
On/Off
default
value is
On for
the first
startup
and the
value is
Off after
preheatin
g is
complete
.)
97.0°C
90°C to 115°C
107.0°C
90°C to 115°C
30%
30% to 100%
100%
30% to 100%
171