Alarm
Alarm Name
ID
301
EEV Low
Superheat Degree
Alarm
302
EEV Low
Superheat Lock
Alarm
303
EEV Drive Alarm
304
EEV Drive Lock
Alarm
Issue 02 (2020-11-09)
System
Possible Causes
Action
The
1. The EEV is faulty or
compressor
shuts down.
2. The cables to the
3. The EEV coil is
4. The plug of the EEV
5. The plug of the EEV
6. The outdoor
The
The EEV Low
compressor
Superheat Alarm is
shuts down.
triggered multiple
(The alarm
times within a
needs to be
specified period of
manually
time.
cleared.)
The
1. The EEV is not
compressor
shuts down.
2. The EEV coil is
3. The EEV drive circuit
The
The EEV Drive Alarm is
compressor
triggered multiple
shuts down.
times within a
specified period of
time.
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
its step is incorrect.
EEV are not properly
connected.
loose.
is loose.
is short-circuited.
temperature sensor
displays an incorrect
temperature or is
faulty.
connected.
short-circuited.
of the indoor unit
main control board
is faulty.
Solution
1. Check and replace
the EEV.
2. Check and replace
the EEV body.
3. Secure the EEV coil.
4. Secure the plug.
5. Eliminate the short-
circuit fault.
6. Adjust or replace
the outdoor
temperature sensor.
Refer to the solution to
the EEV Low Superheat
Alarm.
1. Check the cables to
the EEV.
2. Check whether the
EEV coil is short-
circuited.
3. Replace the main
control board of the
indoor unit.
Refer to the solution to
the EEV Drive Alarm.