NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Alarm
Alarm Name
ID
105
InFan Run
Timeout Alarm
106
Air Filter Run
Timeout Alarm
201
Comp Discharge
HP Alarm
202
Comp Discharge
HP Lock Alarm
Issue 02 (2020-11-09)
System
Possible Causes
Action
--
The runtime of the
indoor fan exceeds the
preset threshold.
--
The runtime of the air
filter exceeds the
preset threshold.
The
1. The condenser fins
compressor
shuts down.
2. The outdoor fan or
3. The high pressure
4. The high pressure
5. The refrigerant is
6. The outdoor unit is
The
The Comp Discharge
compressor
HP Alarm is triggered
shuts down.
multiple times within a
(The alarm
specified period of
needs to be
time.
manually
cleared.)
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
are dirty or blocked.
its drive is faulty.
sensor cable is not
properly connected.
sensor is faulty.
overfilled.
not properly
installed.
Solution
Replace the indoor fan
and clear the
cumulative runtime.
Replace the air filter
and clear the
cumulative runtime.
1. Clean the condenser
fins.
2. Maintain or replace
the outdoor fan
drive or outdoor
fan.
3. Check the cable
connections to the
high pressure
sensor.
4. Maintain or replace
the high pressure
sensor.
5. Decrease certain
amount of
refrigerant.
6. Reinstall the
outdoor unit.
Refer to the solution to
the Comp Discharge
HP Alarm.