3.11 Connecting the NetCol5000-C with a Server Cabinet
in Parallel
Prerequisites
For the narrow space and difficult for maintenance after combining the cabinet, install the
water pipe adaptor before combining the cabinet, for the details, refer
Water Pipe
Procedure
Step 1 Reinstall the side panel by referring to
removed, skip this step.
Step 2 Remove the lower screws from the two connecting plates.
Step 3 Secure the lower screws to a server cabinet to connect the NetCol5000-C with the server
cabinet in parallel.
----End

3.12 Connecting Pipelines

This topic describes how to connect pipelines for NetCol5000-C. You can choose NetCol520
(optional) to be liquid distribution unit for NetCol5000-C, can also be configured separately
according to the site conditions. If you select NetCol520 liquid distribution unit, for details
about the operations, see NetCol Liquid Distribution Unit User Manual.

3.12.1 Exhausting Nitrogen

Procedure
Step 1 Loosen the air exhaust valve to exhaust nitrogen. Fasten the air exhaust valve until no air
exhaust from the exhaust valve, as shown in
Figure 3-15 Exhausting nitrogen
----End