Cool Wall Clearances

The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
G600EC Clearance Requirements—Cool Wall Installations
Clearance:
A: Mantel Height (min.)
B: Sidewall
C: Ceiling
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
G: Convection Air Outlet
H: Convection Air Outlet Opening Offset
K: Chase Enclosure (Min.)
L: Clearance to Sprinkler Head (Min.)
Notes:
IMPORTANT - *A minimum of 58 square inches of open area, not lower than 0"-2" from top of enclosure, required
for all cool wall installations — this can be achieved by having an open area in front. See manual for details.
** An extra 3/4" (19mm)of mantel height is required when using a faceplate.
C
D
K
E
F
Alcove
greatest importance that this fireplace and vent system be installed only in accordance
Cool Wall - Clean Front
Measured From:
1" (25 mm)**
Top of Fireplace Opening
6" (152 mm)
Side of Fireplace Opening
44-1/4" (1124 mm)
Top of Fireplace Opening
12" (305 mm)
Front of Fireplace Opening
84" (2134 mm)
Wall to Wall (Minimum)
36" (914 mm)
Front to Back Wall (Maximum)
58 in
2
(375 cm
2
)*
Top/Front of Enclosure
0-2" (0-51 mm)
*Top of Chase Enclosure
74-1/2" (1892 mm)
From Base of Appliance Floor
36" (914 mm)
Perpendicular From Chase Grill
0"
No Hearth Required
Fire hazard is an extreme risk
If these clearances (air space) to combustible materials are not adhered to. It is of
with these instructions.
L
Chase grill
Side view
Minimum Vent Clearances
to Combustibles
Horizontal Top
2" (51mm)
Horizontal Side
1-1/2 " (38mm)
Horizontal Bottom
1-1/2" (38mm)
Vertical Vent
1-1/2" (38mm)
installation
WARNING
The HeatWave Duct Kit
has different clearance
and framing require-
ments, check the Heat-
Wave manual for details.
Sprinkler
Grandview® G600EC Gas Fireplace
|
25