Commissioning; Mag 5000/6000 Blind - Siemens SITRANS F M MAG 5000 Manual

Hide thumbs Also See for SITRANS F M MAG 5000:
Table of Contents

Advertisement

6

Commissioning

6.1
Changing settings
www.eltra-trade.com
In this chapter it is described how to commission the device via the local user interface (LUI).
The display is described in details in section Local user interface (Page 40).
Furthermore, the following functions are described in details:
● Changing password (Page 42)
● Changing basic settings (Page 43)
● Changing operator menu setup (Page 45)
● Changing language (Page 46)
Detailed diagrams concerning the specific menu are shown in appendix menu diagrams.
For factory settings, see Factory settings.

MAG 5000/6000 Blind

Note
Does not have a display. All factory settings will be uploaded from the SENSORPROM
after power-up.
For sensor dependent factory settings, see Appendix B.
If other settings are required, a standard transmitter with display and similar power supply
can be used.
1. Unscrew and remove MAG 5000/6000 Blind.
2. Mount standard MAG 5000/6000 transmitter.
3. Change required settings via display and keypad.
All changed data will be stored in SENSORPROM
4. Remove standard transmitter and remount Blind transmitter.
5. Fasten screws holding transmitter.
New settings stored in SENSORPROM
memory unit will be uploaded in blind transmitter.
®