MODEL X5200M
The X5200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with
unusual chemistry such as black powder. Consult factory for usage recommendations.
X5200M RESPONSE CHARACTERISTICS
High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Fuel
Size
Black Powder
40 grams
X5200M RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARMS
High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
False Alarm Source
Sunlight, direct, reflected, modulated & unmodulated
70 w sodium vapor lamp, unmodulated
70 w sodium vapor lamp, modulated
250 w vapor lamp, unmodulated
250 w vapor lamp, modulated
300 w incandescent lamp, unmodulated
300 w incandescent lamp, modulated
500 w halogen lamp, unmodulated
500 w halogen lamp, modulated
1500 w electric radiant heater, unmodulated
1500 w electric radiant heater, modulated
2-34 w fluorescent lamps , unmodulated
2-34 w fluorescent lamps , modulated
X5200M FALSE ALARM IMMUNITY
High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
False Alarm Source
Sunlight, direct, reflected
Arc welding
70 w sodium vapor lamp
250 w vapor lamp
300 w incandescent lamp
500 w halogen lamp
1500 w electric radiant heater
2-34 w fluorescent lamps
X5200M FIELD OF VIEW
High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Fuel
Size
Black Powder
40 grams
9.2
FM Approval and Performance Report – Continued
Distance
Typical Response Time
feet (m)
(seconds)
10 (3)
0.12
Distance
feet (m)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
10 (3)
10 (3)
3 (0.9)
3 (0.9)
Distance
Modulated Response
feet (m)
15 (4.6)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
3 (0.9)
Distance
Horizontal
Typical Horz. Response
feet (m)
(degrees)
5
+45
(1.5)
–45
Fire Source
2 inch dia Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
1 x 1 foot n-Heptane
Unodulated Response
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
Time (seconds)
(degrees)
0.1
0.1
27
Distance
Typical Response Time
feet (m)
(seconds)
10 (3)
< 15
40 (12)
5
40 (12)
< 1
40 (12)
11
40 (12)
< 1
40 (12)
7
40 (12)
6
40 (12)
< 1
40 (12)
11
40 (12)
< 1
40 (12)
< 1
40 (12)
15
40 (12)
< 1
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
No alarm
Vertical
Typical Horz. Response
Time (seconds)
+45
0.1
–30
0.1
95-8547