Fig. 5-9 Pin Assignment Of Diagnostic Connector - ABB AC 800F Mounting And Installation Instructions Manual

Hide thumbs Also See for AC 800F:
Table of Contents

Advertisement

5
Diagnostic connector
Use
one
of
TK 890F or TK 891F cables for
connecting a diagnostic interface,
see Section 4.1.5 and Section 5.4.
Technical data of SD 802F
Input voltage
Mains frequency
Protection against polarity reversal
Protection against improper voltage
values and/or frequency
Bridging time in case of power failure
Fuse
Output voltages
Output current
Total output power
Current limiting
Input current at nominal load
Rated input power
Inrush current
Efficiency
Thermal power loss with nominal load
Weight
Connectors
5-8
the
ready-made
Fig. 5-9
Power connector
Diagnostic interface
Module/CPU board
AC 800F Functional Description
Pin assignment of diagnostic connector
24 V DC. Perm. range 19.2 ... 32.5 V DC.
Perm. ripple 14 % peak-peak, supply via
three-phase bridge rectifiers permissible.
DC input, therefore not applicable
yes
application of voltages below nominal
voltage does not cause destruction,
> 20 ms without malfunctions
subminiature fuse type 3.15 AT, in input
circuit, for each supply
3.3 V DC (± 3 %),
5.0 V DC (± 3 %)
0.5 ... 5 A to 3.3V and 5.0V
max. 26.5 W
above approximately 6 A, automatic restart
of normal operation
1.3 A at 24 V DC
31 W
max. 15. times the peak value of the nominal
current (NAMUR)
around 86 %
5 W
460 g
2-pin housing connector GSSA200,
from Hirschmann
9-pin Sub-D connector (male)
96-pin connector