ABB AC 800F Mounting And Installation Instructions Manual page 203

Hide thumbs Also See for AC 800F:
Table of Contents

Advertisement

5
With configured redundancy link (i.e. coding switch on Ethernet module in slot 2 its in
F position):
First Network interface [00:C0:C9:10:00:88] - Cheapernet
- IP address: 172.16.1.1
- Subnet mask: 255.255.240.0
Second Network interface [00:C0:C9:10:1E:EB] - Cheapernet as RedLink
Only if the coding switch of at least one Ethernet module is set to 0 (special case,
expanded network configuration), the Default Router line will appear. The example
above shows a AC 800F with two 10Base2 modules EI 801F. The following line is
indicated if slot E1 or E2 is empty:
First Network interface not available
or
Second Network interface not available
A TDR (Time Domain Reflectometer) test is performed for every Ethernet module
plugged in a slot. If the message
Error: Controller or other network problem
appears, in most cases the module has not been connected properly to the Ethernet
cabling.
The message
Error: Open Line 3 clocks away
indicates a problem with the bus setup, for example a 10Base2 link without a
terminating resistor.
If the message
Error: Short Line 5 clocks away
appears, there is a short-circuit in the transmission path.
If you confirm the message within the waiting time by pressing the space key, the
following message pops up:
<C>hange, set <T>ime, <S>ave or continue <B>ooting?
The system configuration parameters listed below can be changed under menu item
<C>hange:
IP address (with extended network configuration only)
Behavior of the Boot Loader after operating system call
Baud rate of diagnostic interface
Boot Loader waiting time before configuration block startup.
AC 800F Functional Description
5-35