ABB AC 800F Mounting And Installation Instructions Manual page 148

Hide thumbs Also See for AC 800F:
Table of Contents

Advertisement

4
2. FI 820F not installed at the end of the bus cable.
Cable the terminal block TB 870F with the other RS485 nodes on the bus as seen
in Fig. 4-60. Keep the branch cables to the nodes as short as possible.
Fig. 4-60 Cabling FI 820F via RS485 interface, case 2
Provide a termination at both ends of the bus cable, as described above. Use a
shielded TP cable according to the instructions given above.
4-82
Make sure that no jumpers are set on the FI 820F module and
that the switches on the terminal block TB 870F are in the
OFF position.
Remember the terminating resistors at both ends of the bus
cable.
Cabling the AC 800F