5
Setting: Auto Startup:
In this mode the Boot Loader first checks the flash EPROM for an existing and intact
operating system. If no or a corrupted operating system is found, the following
message appears:
No Operating System found !
AMD 29DL800 detected
DFC-BootLoader waiting ...
The program then continues in the line described in the Start-up mode setting.
Force execution of BootLoader
If a valid operating system is found, the RAM is checked for an existing and working
configuration. The message
Checking Configuration... OK !
Startaddress: 0xE00542F0
*** AC 800F Startup Code ***
Version 6.80
appears when a valid project configuration is found. The operating system is started.
After operating system startup, various other initialization messages are displayed
which are not further described here. Commissioning is done via the engineering
station.
If no or a corrupted project configuration is found, the following message appears:
Checking Configuration ... failed !
Using default configuration...
Startaddress: 0xE00542F0
*** AC 800F Startup Code ***
Version 6.80
Startup due to Default Boot
In this case a default configuration is used to be able to start the operating system.
The AC 800F will then wait for the project configuration to be loaded.
(<- this address is an example)