12
Connectors: Did you fasten all connectors with screws?
Cables:
Do all communication cables have a sufficient cross-sectional area?
Did you lay the cable properly, following the instructions?
Did you follow the instructions regarding the use of shielded cables?
Did you observe the max. cable length?
Cable shields: Did you strip off the cable sheath and fasten the cable to the
contact ledge using TV 831F/TV 832F clips (3.4)?
Sec. 4.1 Power supply modules, mains connection
Is the proper power supply used?
SA 801F/SA 811F for 115 - 230 V AC, SD 802F/SD 812F for 24 V DC (4.1)
Is/are the input circuit(s) of the power supply fuse-protected (4.1)?
Is there a 2-pole switch on the power supply input (4.1)?
Did you fasten the connectors with screws to power supply modules?
With SD 802F/SD 812F: Are two power cables provided?
With only one power cable: is the unused connector protected with a dummy
plug?
Diagnostic interface:
Did you mind the fact that connecting a diagnostic PC/terminal may cancel out
the protective separation of the AC 800F?
Do you have a diagnostic cable TK 890F or TK 891F? It is needed for
commissioning.
Is the GND terminal connected?
12-2