Safety Specifications Atex / Iecex; Special Conditions For Type Of Protection "Ex Td" (Dust Explosion Protection) - ABB VA Master FAM540 Commissioning Instructions
Special conditions for type of protection "Ex td" (dust explosion protection)
Model FAM54xB/C/D/E/Fx
The following differing temperature data applies to usage in areas with combustible dust.
Order code
Ambient temperature T
A4, A9, B1
-50°C... +60°C
-50°C... +40°C
-50°C... +20°C
Table 1: Analog indicator with transmitter, with or without LCD indicator
Model FAM54xE/Fx
Type of protection: flameproof enclosure, intrinsic safety, non-sparking equipment, dust explosion protection.
Order
Labeling
code
1)
A4, A9
ATEX:
II 1/2 G Ex c ia IIC T4 ... T1 Ga/Gb
II 2 D Ex tb IIIC T85 ˚C... T
IECEx:
Ex ia IIC T4 ... T1 Ga / Gb
Ex tb IIIC T85 °C ... T
A9
ATEX:
II 1/2G Ex c d IIC T6 ... T1 Ga/Gb
II 2 D Ex tb IIIC T85 ˚C... T
IECEx:
Ex d IIC T6 ... T1 Ga / Gb
Ex tb IIIC T85 °C ... T
A4, A9,
ATEX:
B1
II 1/3G Ex c nA ic IIC T6 ... T1 Ga/Gc
II 2 D Ex tb IIIC T85 ˚C... T
IECEx:
Ex nA ic IIC T6 ... T1 Ga / Gc
Ex tb IIIC T85 °C ... T
1) Order code "Explosion protection and approvals" (versions 9, 10); refer to chapter Ordering information in the data sheet.
2) For connection to an intrinsically safe circuit.
3) For connection to a non-intrinsically safe circuit. If the device is to be operated subsequently with type of protection "intrinsically safe", then U
exceeded.
10 CI/FAM540-EN Rev. B | VA Master FAM540
amb
Terminals Electrical
31 / 32
2)
Db
medium
Db
41 / 42
2)
medium
31 / 32
3)
Db
medium
Db
3)
41 / 42
medium
3)
31 / 32
Db
medium
Db
3)
41 / 42
medium
Maximum permissible measuring medium temperature T