PLC Setup

Word(s)
Bit(s)
AR 21
00 to 07
Day of the Week (00 to 06, BCD)
00: Sunday
(Note 2)
04: Thursday
08 to 12
Not used.
13
30-second Compensation Bit
Turn this bit ON to round off to the nearest minute. When the seconds are 00 to 29, the seconds
are cleared to 00 and the rest of the time setting is left unchanged. When the seconds are 30 to
59, the seconds are cleared to 00 and the time is incremented by one minute.
14
Clock Stop Bit
Turn this bit ON to stop the clock. The time/date can be overwritten while this bit is ON.
15
Clock Set Bit
To change the time/date, turn ON AR 2114, write the new time/date (being sure to leave AR 2114
ON), and then turn this bit ON to enable a new time/date setting. The clock will restart and both
AR 2114 and AR 2115 will be turned OFF automatically.
AR 22
00 to 15
Not used.
AR 23
00 to 15
Power-off Counter (4-digit BCD)
This is the count of the number of times that the power has been turned OFF.
To clear the count, write "0000" from a Programming Device.
Note
4-5

PLC Setup

4-5-1

Changing the PLC Setup

Effectiveness of Changes
82
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
01: Monday
02: Tuesday
05: Friday
06: Saturday
1. The same data can be read immediately with PRV(62).
2. The time and date can be set while AR 2114 is ON. The new setting be-
comes effective when AR 2115 is turned ON. (AR 2114 and AR 2115 are
turned OFF automatically when the new setting goes into effect.)
3. The units for the maximum and current cycle times are determined by the
setting in bits 08 to 15 of DM 6618. A setting of 00 specifies 0.1-ms units,
01 specifies 0.1-ms units, 02 specifies 1-ms units, and 03 specifies 10-ms
units.
The PLC Setup comprises various operating parameters that control PLC
operation. In order to make the maximum use of PLC functionality when using
interrupt processing and communications functions, the PLC Setup may be
customized according to operating conditions.
After the PLC Setup has been changed, be sure to switch the CPM2B to
MONITOR or RUN mode or turn the power OFF and then ON again.
The PLC Setup settings in DM 6600 to DM 6655 can be changed from a Pro-
gramming Device. The CPM2B must be in PROGRAM mode in order to
change the settings in DM 6600 to DM 6644. The settings in DM 6645 to
DM 6655 can be changed in MONITOR or PROGRAM mode, but CPM2B's
cycle time will be long if the settings are changed in MONITOR mode.
All of the PLC Setup settings are set to their defaults when the CPM2B is
shipped. The default values for the PLC Setup are 0000 for all words (except
for the low battery error enable in DM 6655 bits 12 to 15).
PLC Setup settings are accessed at various times depending on the setting,
as described below.
Words
DM 6600 to DM 6614 Accessed only when PLC's power supply is turned ON.
DM 6615 to DM 6644 Accessed only when program execution begins.
DM 6645 to DM 6655 Accessed regularly when the power is ON.
Function
03: Wednesday
Timing
Section 4-5