System Configurations
1-2-7

One-to-N Computer Connections

Using the RS-232C Port
Connecting Cable
XW2Z-@00S-V
IBM PC/AT or
compatible computer
Using the Peripheral Port
Connecting Cable
XW2Z-@00S-V
IBM PC/AT or
compatible computer
Note
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
munications Switch SW201 is ON and DM 6600 of the PLC Setup is set to its
default setting so that the Programming Console's mode switch controls the
startup mode.)
Up to 32 OMRON PLCs, including CPM2B PLCs, can be connected to a host
computer.
3G2A9-AL004-E or NT-AL001-E (requires +5 V)
(See notes 1 and 2.)
RS-422 (Total length: 500 m max.)
NT-AL001-E
(See note 1.)
CPM2B CPU Board
3G2A9-AL004-E or NT-AL001-E (requires +5 V)
(See notes 1.)
RS-422 (Total length: 500 m max.)
CPM1-CIF11
(See note 3.)
CS1W-CN114
CPM2B CPU Board
1. The NT-AL001-E must be supplied externally with 5 V DC. When an NT-
AL001-E is connected to a CPM2B PLC, pin 6 of the CPM2B's RS-232C
port supplies +5 V DC and an external power supply is not necessary.
When the NT-AL001-E is connected to a host computer, it is necessary to
supply 5 V DC from an external power supply.
If an NT-AL001-E is connected to the CPM2B's RS-232C port, only one
Expansion I/O Board can be connected to the CPU Board because the NT-
AL001-E draws its 5-V DC power from the CPU Board.
Use an XW2Z-070T-1 (0.7 m) or XW2Z-200T-1 (2 m) cable to connect the
NT-AL001-E to the CPM2B's RS-232C port.
2. The 3G2A9-AL004-E requires an external AC power supply (110 V AC or
220 V AC).
NT-AL001-E
(See note 1.)
CPM2B CPU Board
Up to 32 PLCs
CQM1H-CIF12
CS1W-CN114
CPM2B CPU Board
Up to 32 PLCs
Section 1-2
NT-AL001-E
(See note 1.)
CPM2B CPU Board
CPM1-CIF11
(See note 3.)
CPM2B CPU Board
13