SR Area
Word(s)
Bit(s)
SR 253
00 to 07
FAL Error Code
The error code (a 2-digit number) is stored here when an error occurs. The FAL number is
stored here when FAL(06) or FALS(07) is executed. This word is reset (to 00) by execut-
ing a FAL 00 instruction or by clearing the error from a Programming Device.
08
Battery Error Flag
Turns ON when the CPU Board backup battery's voltage is too low.
09
Cycle Time Overrun Flag
Turns ON when a cycle time overrun occurs (i.e., when the cycle time exceeds the maxi-
mum cycle time set in the PLC Setup).
10,11
Not used.
12
Changing RS-232C Setup Flag
Turns ON when the RS-232C port's settings are being changed.
13
Always ON Flag
14
Always OFF Flag
15
First Cycle Flag
Turns ON for 1 cycle at the start of operation.
SR 254
00
1-minute clock pulse (30 seconds ON; 30 seconds OFF)
01
0.02-second clock pulse (0.01 second ON; 0.01 second OFF)
02
Negative (N) Flag
Turns ON when the result of a calculation is negative (leftmost bit of binary result ON.)
03
Not used.
04
Overflow (OF) Flag
Turns ON when an overflow occurs in a signed binary calculation.
05
Underflow (UF) Flag
Turns ON when an underflow occurs in a signed binary calculation.
06
Differential Monitor Complete Flag
Turns ON when differential monitoring is completed.
07
STEP(08) Execution Flag
Turns ON for 1 cycle only at the start of process based on STEP(08).
08 to 15
Not used.
SR 255
00
0.1-second clock pulse (0.05 second ON; 0.05 second OFF)
01
0.2-second clock pulse (0.1 second ON; 0.1 second OFF)
02
1.0-second clock pulse (0.5 second ON; 0.5 second OFF)
03
Instruction Execution Error (ER) Flag
Turns ON when an error occurs during execution of an instruction.
04
Carry (CY) Flag
Turns ON when there is a carry in the results of an instruction execution.
05
Greater Than (GR) Flag
Turns ON when the result of a comparison operation is "greater."
06
Equals (EQ) Flag
Turns ON when the result of a comparison operation is "equal," or when the result of an
instruction execution is 0.
07
Less Than (LE) Flag
Turns ON when the result of a comparison operation is "less."
08 to 15
Not used.
78
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Note DM 6601 in the PLC Setup can be set to maintain the previous status of the
Forced Status Hold Bit (SR 25211) and the I/O Hold Bit (SR 25212) when
power is turned OFF. Refer to 4-5 PLC Setup for details.
Function
Section 4-3
Read/
write
Read-
only
Read/
write
Read-
only
Read-
only
Read-
only
Read-
only