This humidity is saved as the first reference
value. No further manual setting of a refe-
rence value is necessary.
If the relative humidity drops directly following
the installation, this is saved as the new refe-
rence value. The lowest possible reference
value is 48 % relative air humidity.
If the room humidity increases by 7 %, the
fan switches on automatically at performance
level 1 (78 m³/h).
● If the room humidity increases even
further, the unit switches to performance
level 2 (92 m³/h).
● If there are no further increases, the unit
continues to run at performance level 1
(78 m³/h) until the humidity again falls
below the saved reference value.
If humidity falls below the reference value,
the performance level is also throttled back.
● If an RLS RC is deployed, operation is
done in line with the setting at the RLS RC.
● In the case of operation without an RLS RC
(individual unit), the unit switches back to
the last performance level to have been
active before humidity operation.
The currently prevailing room humidity is
saved as the new reference value. A new
reference value is also saved if the radio
switch is operated during humidity operation.

3.5 Further radio components

DS RC radio switch
3.5.1
(EnOcean switch)
Fan with a radio switch in individual
operation
● Radio switch, (double-rocker switch) for
setting different fan performance levels.
● Press the rocker switch to switch up or
down one performance level.
The left and right rocker have to be
i
set up separately: Left rocker for
on/off, right rocker to switch the
performance level up and down.
Always set up the radio switch for the
i
fan that is located in the same room
as the switch.
20
Fan with several radio switches in
individual operation
Function as described above. Up to 5 radio
switches can be set up per fan.
Radio switches in master/slave network
The ventilation system is operated as
i
per the settings made at the RLS RC.
However, every switching action
made by radio switch has priority over
the RLS RC setting.
● If a radio switch is operated, the assigned
fan switches to the manually selected
performance level.
● After 30 minutes of the switch not being
operated (timeout), the unit returns to the
setting according to RLS RC. If the setting
is changed at the RLS RC during the
timeout, the assigned fan only reacts to this
command once the timeout has elapsed.
● In the case of the RCH version, the auto-
matic humidity function has priority when
operating in vacation mode. Switching
through the DS RC or through a radio
window contact is possible during humidity
operation.
3.5.2 Radio window contact
(EnOcean switch)
● A maximum of 2 radio window contacts can
be taught-in for each fan.
● The radio window contact sends the
"Window open" or "Window closed" status
to the assigned fan.
● The assigned fan switches off
automatically if the window is opened.
● If you want the fan to continue to operate
even when the window is open, it can be
switched on with the assigned radio switch.
● The radio switch has priority over the radio
window contact and/or the RLS RC.
● The fan either switches off again after a
timeout of approx. 30 minutes if the window
is still open or back to the operation mode
set through the RLS RC if the window is
closed.