Par. No.
Name
p29341
Warning 2 assigned for
digital output
Description: Defines conditions for WARNING2.
1: Motor overload protection warning: 85% of overload threshold has been reached.
2: Holding brake power overload warning: threshold p29005 has been reached.
3: Fan warning: life time of fan expired (40000 hours), replacement of fan needed.
4: Encoder warning
5: Motor overtemperature warning: 85% of overtemperature threshold has been reached.
6: Capacitor service life warning: The capacitor has reached its expiry, so replace it.
p29350
Select sources for analog
output 1
Description: Selects signal source for analog output 1.
0: Actual speed (reference p29060)
1: Actual torque (reference 3 × r0333)
2: Speed setpoint (reference p29060)
3: Torque setpoint (reference 3 × r0333)
4: DC bus voltage (reference 1000 V)
5: Pulse input frequency (reference 1k)
6: Pulse input frequency (reference 10k)
7: Pulse input frequency (reference 100k)
8: Pulse input frequency (reference 1000k)
9: Remaining number of pulses (reference 1k)
10: Remaining number of pulses (reference 10k)
11: Remaining number of pulses (reference 100k)
12: Remaining number of pulses (reference 1000k)
p29351
Select signal source for
analog 2
Description: Selects signals for analog output 2.
0: Actual speed (reference p29060)
1: Actual torque (reference 3 × r0333)
2: Speed setpoint (reference p29060)
3: Torque setpoint (reference 3 × r0333)
4: DC bus voltage (reference 1000 V)
5: Pulse input frequency (reference 1k)
6: Pulse input frequency (reference 10k)
7: Pulse input frequency (reference 100k)
8: Pulse input frequency (reference 1000k)
9: Remaining number of pulses (reference 1k)
10: Remaining number of pulses (reference 10k)
11: Remaining number of pulses (reference 100k)
12: Remaining number of pulses (reference 1000k)
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
Min
Max
1
6
0
12
0
12
Factory
Unit
Data
Setting
type
2
-
U16
0
-
U16
1
-
U16
Parameters
10.2 Parameter list
Effective
Can be
changed
IM
T
IM
T
IM
T
373