Siemens Sinamics V90 Operating Instructions Manual page 370

Pulse train, uss/modbus interface
Hide thumbs Also See for Sinamics V90:
Table of Contents

Advertisement

Parameters
10.2 Parameter list
Par. No.
Name
p29243
Positioning tracking acti-
vate
Description: Activation of position tracking.
0: Deactivated
1: Activated
p29244
Absolute encoder virtual
rotary revolutions
Description: Sets the number of rotations that can be resolved for an encoder with activated position tracking
function (p29243 = 1).
p29245
Axis mode state
Description: Linear/modulo mode:
0: Linear axis
1: Modulo axis
p29246 *
Modulo correction range
Description: Sets the modulo range for axes with modulo correction.
p29247 *
Mechanical gear: LU per
revolution
Description: LU per load revolution.
p29248 *
Mechanical gear: Numer-
ator
Description: (Load/Motor) Load revolutions.
p29249 *
Mechanical gear: denom-
inator
Description: (Load/Motor) Motor revolutions.
p29250
PTI absolute position
mode enable
Description: Absolute position mode enable.
1: Enable Absolute Mode
0: Disable Absolute Mode
p29300
Digital input forced sig-
nals
Description: assignment signals are forced to be high. 7 bits in total.
Bit 0: SON
Bit 1: CWL
Bit 2: CCWL
Bit 3: TLIM1
Bit 4: SPD1
Bit 5: TSET
Bit 6: EMGS
If one or more bits are set to be high, the corresponding input signals are forced to be logical high signals.
Note: The drive unit displays the value in hex format. To know the logic (high/low) assignment to each bit, you
must convert the hex number to the binary number, for example, FF (hex) = 11111111 (bin).
368
Min
Max
0
1
0
4096
0
1
1
214748264
7
1
214748364
7
1
1048576
1
1048576
0
1
0
127
Factory
Unit
Data
Setting
type
0
-
I16
0
-
U32
0
-
U32
360000
LU
U32
10000
-
U32
1
-
U32
1
-
U32
0
-
U32
0
-
U32
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
Effective
Can be
changed
IM
T
IM
T
IM
T
IM
T
IM
T
IM
T
IM
T
RE
T
IM
T, U

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics s-1fl6

Table of Contents