DV50 DV80
(Integral CO
Sensor)
2
POWER SUPPLY
Maximum
≤6W
Adroit digital
1W
Controller
Adroit RH%
0.3W
transmitter
Adroit CO
1.2W
2
transmitter
Voltage
24 VDC
External
temperature
sensor
2x0,5
NTC 4K7
2x0,5
Digital input 1
Digital input 2
8 different
functions
Ethernet connection
on top of the unit
CAT
RJ45 female
MB_A
External Modbus A signal
MB_B
External Modbus B signal
+24V
+24V direct current voltage (DC)
GND
Digital and analog ground potential
RS_A
Local hardware Modbus A signal
RS_B
Local hardware Modbus B signal
NTC
External temperature sensor connector
Adroit
RH%
MONITORING
transmitter
2x2x0,5+0,5
Adroit
CO
2
transmitter
2x2x0,5+0,5
2x0,5
8 different
functions
VENTILATION UNIT INTERNAL
ELECTRICAL CONNECTION
EXTERNAL ELECTRICAL CONNECTION
REMOTE
Modbus RTU
2x2x0,5+0,5
D/I1
Digital input 1
D/I2
Digital input 2
11V1
11.1 V operating voltage
AN/I
Analog input 0-10 VDC
RM/I
24 V relay input
RM/O
24 V relay output
46
7028350
2014-08-29 JS
Adroit
Digital
Controller
2x2x0,5+0,5
Adroit
Digital
Controller
2x2x0,5+0,5
Analog input
two different
2x0,5
functions
2x0,5
Potential-free contact
data 24VDC can be
programmed to display
information such as
errors or the status of the
cell bypass
Power supply cable
3x1,5S