INSTALLATION

INSTALLATION SITE
DV 50 / 80 must be installed in a location where the
temperature remains above +10 °C. When the unit is
installed without a protective enclosure, the location must
be chosen so that its noise does not cause any disturbance.
Such locations include storage premises, technical spaces,
and false ceilings.
NOTE
The whole length of the outdoor air duct to the unit and
exhaust ait duct from the unit must be insulated using closed
cell insulation.
MOUNTING
The ventilation unit is normally installed on the ceiling using
the mounting hooks (4) delivered with the unit. The weight of
the unit (45 kg) must be taken into account when mounting
!
the unit.
WARNING
a
The unit must be installed straight so that the condensing
water that collects in the bottom pool drains through the
condensing water outlet.
a
NOTE
Reserve a space equal to the depth of the unit in front of the
unit for servicing purposes.

MEASURING TUBES

The accessories delivered with the unit include four ADROIT
measuring tubes. These can be inserted in the ducts to
allow for easier ventilation adjustment.