Flashing Light Signals; Control Unit Signals - Nice Filo Instructions And Warnings For Installation

Table of Contents

Advertisement

9.10.2 - Flashing light signals

Flashes (quick)
Status
ECSBus error
1 second pause
Intervention of a photocell
1 second pause
1 second pause
activated
Intervention of the Stop input
1 second pause
Error in the internal parameters of
1 second pause
the electronic control unit
The maximum manoeuvre limit per
1 second pause
hour has been exceeded
Error in the internal electric circuits
1 second pause
A command that does not allow
1 second pause
other commands to be executed is
already present
The automation is locked
1 second pause

9.10.3 - Control unit signals

On the control unit there are LEDs (Fig. 8 )
Led ECSBus
Status
O
Fault
On
Serious fault
Input status variation
-
Flashing light signal see Table 7
rated by a pause
ECSBus short-circuit
Stop led
Status
O *
Intervention of the Stop input
On
SbS led
Status
O
On
Intervention of the SbS input
L4 led
Status
O *
On
Memorisation in Mode 1
A series of quick
Memorisation in Mode 2
Incorrect command
15 – English
TABLE 8
Action
At the beginning of the manoeuvre the devices present do not match those reco -
check to see if there are any obstructions.
identify the cause
means there is a serious malfunction and the electronic board must be replaced
Wait a few minutes until the manoeuvre limiting device drops below the maximum
limit
Disconnect all the power circuits for a few seconds and then try giving a command
tronic board has to be replaced
Check the type of command that is always present (for example, it may be a com
mand from a clock on the SbS input)
Release the automation by sending an automation release command to the con
trol unit
TABLE 9
Action
tify the reason for the failure then replace them with others of the same type
condition persists, it means that there is a malfunction and the electronic circuit
board has to be replaced
Control unit works correctly
of photocells or the radio transmitter is used
(after a brief delay)
An overload has been detected therefore the power to the ECSBus was switched
o . To verify, disconnect one device at a time.
To activate power to the ECSBus, simply give a command (for example, through
the transmitter)
Action
Check the devices connected to the Stop input
Stop input active
Action
OPEN input not active
Normal only if the device connected to the SbS input is actually active
Action
No Memorisation in progress
During memorisation in Mode 1, it is normal for it to last maximum 10 seconds.
During memorisation in Mode 2, it is normal for it to last maximum 10 seconds.
Successful deletion of a transmitter
A command has been received from a non-memorised transmitter
Memorisation completed successfully
Deletion of all transmitters completed successfully
Table 8.
see Table 9.
-
-
-
-