Appendix C: Sensor Resistance/Voltage Chart - Watts AERCO Benchmark BMK 1500DF User Manual

Natural gas, propane gas, or dual fuel fired modulating, condensing boilers
Table of Contents

Advertisement

Benchmark 750-3000 Operation, Service & Maintenance Guide-Latin America
APPENDIX C – SENSOR RESISTANCE/VOLTAGE CHART

Appendix C: SENSOR RESISTANCE/VOLTAGE CHART

Temperature Sensor Resistance Voltage Chart (BALCO)
TEMPERATURE
°F
°C
-40
-40
-30
-34.4
-20
-28.9
-10
-23.3
0
-17.2
10
-12.2
20
-6.7
30
-1.1
40
4.4
50
10
60
15.5
70
21.1
80
26.7
90
32.2
100
37.8
110
43.3
120
48.9
130
54.4
140
60
150
65.6
160
71.1
170
76.7
180
82.2
190
87.8
200
93.3
210
98.9
220
104.4
230
110
240
115.6
250
121.1
OMM-0132A
GF-206-LA-LA
RES (OHMS)
779.0
797.5
816.3
835.4
854.8
874.6
894.7
915.1
935.9
956.9
978.3
1000.0
1022.0
1044.4
1067.0
1090.0
1113.3
1137.0
1160.9
1185.2
1209.5
1234.7
1260.0
1285.6
1311.4
1337.7
1364.2
1391.0
1418.2
1445.7
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
VOLTS*
1.93
1.96
1.99
2.02
2.05
2.07
2.10
2.12
2.15
2.17
2.20
2.23
2.25
2.27
2.30
2.32
2.34
2.36
2.39
2.41
2.43
2.45
2.47
2.50
2.52
2.54
2.56
2.58
Page 87 of 162