Section 3 Programming
3) Set the "Mode Selection", "Count mode", and "Terminal selection" for the channel to be used, and then click the [OK] button.
<Setting item and range>
Item
Mode selection
High-speed counter mode
setting
(Only when high-speed
counter mode is selected)
A phase / B phase / Mask
/ Clear / Latch
*2, *3
Polarity setting
*1 The direction signal is set to "Soft direction"and an input address is specified for B-phase, the direction signal command
operates by the input address or internal special relay.
*2 When "90-degree phase-differential two-phase signal" is selected for the high-speed counter mode, an input address of the
same response speed must be specified for A-phase and B-phase.
*3 Mask/Clear operates by the parameter setting or internal special relay.
Setting range
Not use / Delay timer mode / High-speed counter mode
U/D 1 multiplication
Forward pulse (A-phase) / Reverse pulse (B-phase) 1 multiplication
U/D 2 multiplication
Forward pulse (A-phase) / Reverse pulse (B-phase) 2 multiplication
P/R 1 multiplication
Command pulse (A-phase) / Direction signal (B-phase) 1 multiplication
P/R 2 multiplication
Command pulse (A-phase) / Direction signal (B-phase) 2 multiplication
P/R (App.Ctrl)
Command pulse (A-phase) / Direction signal 1 multiplication *1
1 multiplication
P/R (App.Ctrl)
Command pulse (A-phase) / Direction signal 2 multiplication *1
2 multiplication
A/B 1 multiplication
90-degree phase-differential two-phase signal 1 multiplication
A/B 2 multiplication
90-degree phase-differential two-phase signal 2 multiplication
A/B 3 multiplication
90-degree phase-differential two-phase signal 3 multiplication
A/B 4 multiplication
90-degree phase-differential two-phase signal 4 multiplication
Basic unit with 14 points: X0 to X7
Basic unit with 24 points: X0 to X11
Basic unit with 32 points: X0 to X19
Basic unit with 40 points: X0 to X23
Basic unit with 60 points: X0 to X35
Positive or Negative
Note: The response speed differs depending
on the address to be used.