Specifications
2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals in
each connector. Connect power supply wiring to every COM terminal, even though the COM terminals in
each connector are connected internally.
DC Input Unit C200H-ID216 (32 Points)
Circuit Configuration and Simultaneously Usable Points
COM
1000 pF
IN00
A
IN07
COM
IN08
5.6 kW
IN15
COM
1000 pF
IN00
B
IN07
COM
IN08
5.6 kW
IN15
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Weight
Dimensions
680 W
Input indicator
Internal
Circuit
680 W
Input indicator
24 VDC
20.4 to 26.4 VDC
5.6 kW
4.1 mA (at 24 VDC)
14.4 VDC min.
5.0 VDC max.
1.0 ms max.
1.0 ms max.
1 (32 points/common)
All 32 points cannot be turned ON simultaneously
at high temperatures. Refer to the following graph.
100 mA 5 VDC max.
180 g max.
C-shape
32
30
25
20
15
10
5
0
0
10
20
30
Ambient Temperature (°C)
Appendix B
Input Voltage: 26.4 VDC
40
50 55 60