Omron SYSMAC C200HS Installation Manual page 146

Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Specifications
Transistor Output Unit C200H-OD212
Circuit Configuration
Note 1. No blown fuse detector circuit is provided.
2. Check the fuse when there is no output.
Terminal Connections
Note 1. Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF.
2. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.
132
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Internal
Fuse
Circuit
Fuse: UL-TSC-8A-N1 (Nagasawa)
8 A 125 V 5.2-dia  20
L
L
L
24 VDC
L
(0.3 A max )
L
L
L
L
COM (OV)
+10%
0.3 A 24 VDC
/
–15%
None
0.1 mA max.
1.4 V max.
0.2 ms max.
0.3 ms max.
1 (16 points/common)
180 mA 5 VDC max.
8 A 125 V (5.2-dia.x20)
+10%
35 mA 24 VDC
/
–15%
350 g max.
B-shape
OUT
L
+ V
OUT
L
24 VDC
COM
0
B0
L
1
A0
2
B1
L
3
A1
4
B2
L
5
A2
6
B3
L
7
A3
8
B4
L
9
A4
10
B5
L
11
A5
12
B6
13
L
A6
14
B7
15
L
A7
B8
NC
A8
+ 24 VDC
B9
Appendix B
(4.8 A/Unit)
min.