Omron SYSMAC C200HS Installation Manual page 124

Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Specifications
No-Voltage Contact Input Unit C200H-ID001
Circuit Configuration
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion
I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM termi-
nals.
Terminal Connections
110
Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Weight
Dimensions
Current
IN
3 kW
IN
1.8
0.01
W
m
k
F
COM
Input indicator
0.3 A
24 VDC
Power
CPU, Expansion I/O Power Supply,
supply
Remote I/O Slave Unit
Current
(NPN output)
No-voltage contact/NPN output type (negative
common)
3 kW
7 mA typical
(14.4 VDC min.)
(5.0 VDC max.)
1.5 ms max. (no-voltage contact, at 25°C)
1.5 ms max. (no-voltage contact, at 25°C)
1 (8 points/common)
10 mA 5 VDC max.
200 g max.
A-shape
Internal
Circuit
+
Internal 24-VDC
power supply
0
A0
1
A1
2
A2
3
A3
4
A4
5
A5
6
A6
7
A7
COM
A8
A9
NC
Appendix B

Advertisement

Table of Contents
loading

Table of Contents