Specifications
Triac Output Unit C200H-OA121-E
Circuit Configuration
Note When the fuse blows, F indicator lights and bit 08 turns ON. Bits 08 through15 cannot be used as IR bits.
Terminal Connections
116
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output LED
indicator
Internal
circuit
Fuse blowout
detection circuit
F indicator
Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
L
L
L
L
120 VAC max.
L
(1 A max. 4 A/Unit)
L
L
L
1 A 120 VAC, 50/60 Hz (4 A/Unit)
10 mA (resistive load)/40 mA (inductive load)
10 VAC
3 mA (100 VAC) max.
1.2 V max.
1 ms max.
1/2 of load frequency or less.
1 (8 points/common)
140 mA 5 VDC max.
5 A 125 V (5.2-dia.x20)
N/A
250 g max.
A-shape
OUT
L
OUT
L
Fuse
COM
120 VAC max.
0
A0
1
A1
2
A2
3
A3
4
A4
5
A5
6
A6
7
A7
A8
COM
A9
NC