Omron SYSMAC C200HS Installation Manual page 133

Hide thumbs Also See for SYSMAC C200HS:
Table of Contents

Advertisement

Specifications
Triac Output Unit C200H-OA223
Circuit Configuration
Internal
Circuit
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits.
Terminal Connections
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output indicator
Fuse: 5 A 250 V (5.2-dia.x20) HT (SOC)
250 VAC max.
(1.2 A max. 4 A/Unit)
1.2 A 250 VAC, 50/60 Hz (4 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
1.5 mA (120 VAC) max./3 mA (240 VAC) max.
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency+1 ms or less.
1 (8 points/common)
180 mA 5 VDC max.
5 A 250 V (5.2-dia.x20)
N/A
300 g max.
E-shape
OUT
L
OUT
L
Fuse
COM
250 VAC max.
Fuse blowout
detection circuit
F indicator
0
L
A0
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
L
A8
COM
A9
NC
Appendix B