Special I/O Units

5-4

Special I/O Units

5-4-1 Required Mounting Conditions

A
High-speed Counter Units
Position Control Units
(NC111/112)
ASCII Units
Analog I/O Units
ID Sensor Units
Fuzzy Logic Units
4 units max.

5-4-2 Special I/O Units and Functions

High-density I/O Units
(Special I/O Units)
It is possible to connect a variety of Special I/O Units to the C200HS in the same
way as the C200H.
A maximum of 10 Special I/O Units including PC Link Units can be mounted to
any slot of CPU, Expansion I/O, and Slave Racks. I/O word numbers 100 to 199
and DM 1000 to DM 1999 are allocated to each Special I/O Unit.
High-density I/O Units can be mounted Remote I/O Slave Units only when the
Remote I/O Slave Units are connected to C200H-RM001-PV1 or C200H-
RM201 Remote I/O Master Units.
The number of Special I/O Units used with a Slave Rack is limited by data trans-
mission considerations, as shown in the table below. The numbers in the table
indicate the maximum number of Units of groups A, B, C, or D which can be used
with a single Slave Rack.
B
High-density and Mixed I/O
Units
Temperature Control Units
Cam Positioner Units
Heat/Cool Temperature
Control Unit
PID Control Unit
8 units max.
Note
1. When a combination of Units from groups A, B, C, and D is used, the number
from each group must satisfy both the following equations:
3A + B + 2C + 6D ≤ 12
A + B + C + D ≤ 8
2. Other Units can be added until the total number of Units reaches ten. If PC
Link Units are used, the number of Units including the PC Link Units must
not exceed ten.
Refer to page 103 for the specifications of each Special I/O Unit.
The TTL Input Unit, DC Input Unit, TTL Output Unit, Transistor Output Unit, TTL
I/O Unit, and DC Input/Transistor Output Unit are High-density I/O Units.
The C200H-ID501, C200H-OD501, and C200H-MD501 are I/O Units for the
TTL Unit.
Eight input points each of the C200H-ID501, C200H-ID215, C200H-MD501,
C200H-MD115, and C200H-MD215 can be set for pulse input.
A High-density I/O Unit can retrieve pulse input, which is shorter in length than
that of the High-density I/O Unit cycle time, as an input signal when the High-
density I/O Unit is set for pulse input.
C
Temperature Sensor Units
Voice Units
6 units max.
Section 5-4
D
Position Control Units
(NC211)
2 units max.
67