Calendar Override Setting (606 Only); System Selection; Programmed Settings - Pentair AUTOTROL 368 Installer Manual

Table of Contents

Advertisement

1. Press
until desired capacity appears then release.
ð Range from 0.4 to 9.5 m
3
from 0.4 m
(12 increments);
3
from 1.0 m
(20 increments);
3
from 3.0 m
(10 increments);
3
from 5.0 m
(10 increments).
6.8
Calendar override setting (606 only)
The 606 controller needs a method to set days between regeneration for regulatory requirements
and in cases when the flow sensor has failed.
1. Press and hold
ð The programmed calendar override is displayed.
2. Press
to increases value.
ð Range from 0 through 30;
0 = Disabled;
0.3 = Regeneration every 8 hours: at 2, 10 and 18 hours;
0.5 = Regeneration every 12 hours: at 2 and 14 hours;
1 – 30 = Regeneration every X days (every 3 days in this
example).
6.9

System selection

The 604 / 606 controller has four system settings available. The system selections accommodate
multiple tank sizes and various feedwater conditions.
System selection:
1. Press and hold
ð A small "u" will be displayed in the left digit.
ð The right digit will display the current system setting.
2. Press
until desired system setting appears then release.
ð The displayed system setting will be stored in flash
memory when the controller exits programming after
5 seconds.
6.9.1

Programmed settings

C#
Cycle
C1
Backwash
Ref. MKT-IM-007 / D - 09.10.2020
3
;
3
to 1.0 m
by increments of 0.05 m
3
to 3.0 m
by increments of 0.1 m
3
to 5.0 m
by increments of 0.2 m
3
to 9.5 m
by increments of 0.5 m
and
for 3 seconds.
and
simultaneously for 3 seconds.
Resin bed
System u1
flow
[minutes]
direction
Installer manual Autotrol 368 (604-606) - Programming
3
3
3
3
System u2
[minutes]
8
8
System u3
System u4
[minutes]
[minutes]
1
3
35 / 60