PROGRAMMING - 368/604

Figure 15
Time of Day: Press
until desired hour appears. Release.
Range: 0 through 23 hours
NOTE: The elapsed minutes will reset to zero when the hours
are changed.
Figure 16
Regenerant Dosage: Press
appears. Release.
Range: 0.5 lbs to 30 lbs
0.5 lbs to 5.0 lbs by increments of 0.5 lbs (10 increments)
6.0 lbs to 30 lbs by increments of 1.0 lbs (25 increments)
Default: 3.0 lbs
Range: 0.20 kg to 6.0 kg
0.20 kg to 1.0 kg by increments of 0.05 kg
1.0 kg to 3.0 kg by increments of 0.1 kg
3.0 kg to 60 kg by increments of 0.5 kg
Default: 0.6 kg
Figure 17
Regen Interval: Press
until desired interval appears.
Release.
Range: 0 through 30
0 = Disabled
0.3 = Regeneration every 8 hours: at 2, 10 and 18 hrs
0.5 = Regeneration every 12 hours: at 2 and 14 hrs
1-30 = Days: 2
Programming is complete.
until desired regenerant dosage

PROGRAMMING - 368/606

Figure 18
Time of Day: Press
until desired hour appears. Release.
Range: 0 through 23 hours
NOTE: The elapsed minutes will reset to zero when the hours
are changed.
Figure 19
Regenerant Dosage: Press
appears. Release.
Range: 0.5 lbs to 30 lbs
0.5 lbs to 5.0 lbs by increments of 0.5 lbs (10 increments)
6.0 lbs to 30 lbs by increments of 1.0 lbs (25 increments)
Default: 30 lbs
Range: 0.20 kg to 6.0 kg
0.20 kg to 1.0 kg by increments of 0.05 kg (16 increments)
1.0 kg to 3.0 kg by increments of 0.1 kg (20 increments)
3.0 kg to 60 kg by increments of 0.5 kg (6 increments)
Default: 0.6 kg
Figure 20
until desired regenerant dosage
AUTOTROL 368 Service Manual• 9