7.1 Working conditions diode display

Readiness for operation
Flap closes
Backwater
Flap is closed
The alarm can be acknowledged with the
test key, i.e. the alarm signal is switched
off during the backwater.
In mains operation, this is indicated by the
alarm LED flashing. All the other optical
displays do not change.
In battery operation, the backwater is in-
dicated by the backwater LED flashing
every second, all other optical displays re-
main dark

2 Device function keys

Alarm key
The alarm can be acknowledged by pres-
sing the alarm key. The alarm-LED flashes
and thus indicates to the operator that the
fault is still pending.
Test key (TEST)
The operating valve can be actuated ma-
nually e.g. for maintenance purposes. The
flap is closed by pressing it once.
The flap is opened again if pressed a se-
cond time.
Closing and opening of the flap is indica-
ted by flashing, the closed flap by the flap
LED lighting up. When the flap is closed,
an acoustic signal (alarm) is given.
Caution: flap does not open automati-
cally!
If backwater occurs while the flap is clo-
sing, this is indicated by the backwater
LED flashing as soon as the flap has been
closed completely. In addition, an alarm is
7. Operating the Comfort control unit
Power-LED
Alarm-LED
Power-LED
Alarm-LED
Backwater-LED orange
FlapLED
Power-LED
Alarm-LED
Backwater-LED orange
Flap-LED
Acoustic Alarm
sounded. During backwater the flap can-
not be opened manually.
Caution:
The end of the backwater is indicated by
the backwater LED going out (optical indi-
cation only ).
The alarm tone no longer changes.
The flap can be opened again using the
test key.
The test key cannot be activated in battery
operation in order to go easy on the bat-
teries
Mains operation
green
lit
red
off
green
lit
red
off
blinks
orange
blinks
green
lit
red
off
blinks
orange
lit
Acoustic Alarm
39
Battery operation
off
blinks (1 sec. Takt)
off
off
off
blinks (1 sec. Takt)
off
off
blinks
off
Acoustic Alarm

7.3 Putting the unit out of operation

Caution: After the mains plug has been
disconnected,
the
alarm
must be pressed for at least 5 seconds
until the signal is sounded. This is to de-
activate the battery.
key
Alarm-key
Test-key