Working Conditions; Function Keys - Kessel Staufix FKA Standard Installation And Operating Manual

Table of Contents

Advertisement

Available languages

Available languages

4.1 Working conditions

Readiness for operation
Flap closes
Backwater
Flap is closed
The alarm can be acknowledged with the test key, i.e. the
alarm signal is switched off during the backwater.
In mains operation, this is indicated by the alarm LED flas-
hing. All the other optical displays do not change.

4.2 Function keys

Alarm key
The alarm can be acknowledged by pres-
sing the alarm key. The alarm-LED flas-
hes and thus indicates to the operator that
the fault is still pending.
Test key (TEST)
The operating valve can be actuated ma-
nually e.g. for maintenance purposes.
The flap is closed by pressing it once.
The flap is opened again if pressed a se-
cond time.
Closing and opening of the flap is indica-
ted by flashing, the closed flap by the flap
LED lighting up. When the flap is closed,
an acoustic signal (alarm) is given.
Caution: flap does not open automati-
cally!
If backwater occurs while the flap is clo-
sing, this is indicated by the backwater
LED flashing as soon as the flap has been
closed completely.
4. Operating the Standard control unit
Power-LED
Alarm-LED
Power-LED
Alarm-LED
Backwater-LED orange
FlapLED
Power-LED
Alarm-LED
Backwater-LED orange
Flap-LED
Acoustic Alarm
Caution: The end of the backwater is in-
dicated by the backwater LED going out
(optical indication only ). The alarm tone
no longer changes.
During backwater the flap cannot be ope-
ned manually.
Caution: The end of the backwater is in-
dicated by the backwater LED going out
(optical indication only ). The alarm tone
no longer changes.
The flap can be opened again using the
test key.
The test key cannot be activated in bat-
tery operation in order to go easy on the
batteries
4.3 Putting the unit out of operation
Caution: After the mains plug has been
disconnected,
must be pressed for at least 5 seconds
until the signal is sounded. This is to go
easy on the battery
Mains operation
green
lit
red
off
green
lit
red
off
blinks
orange
blinks
green
lit
red
off
blinks
orange
lit
Acoustic Alarm
In battery operation, the backwater is indicated by the
backwater LED flashing every second, all other optical dis-
plays remain dark.
the
alarm
key
35
Battery operation
off
blinks (1 sec. Takt)
off
off
off
blinks (1 sec. Takt)
off
off
blinks
off
Acoustic Alarm

Advertisement

Table of Contents
loading

This manual is also suitable for:

Staufix fka comfort

Table of Contents