A1-User's Manual
6) Internal Wiring
Control circuit wires are insulated from power
lines (R,S,T,U,V,W)
Use twisted screened cable for input and
output wires of the control circuit terminals
Limit the connection wires to 65 feet
Separate the control circuit wiring from the
main power and relay control wiring
When using relays for the FW terminal or an
intelligent input terminal, use a control relay
that is designed to work with 24 Vdc.
When a relay is used as an intelligent output,
connect a diode for surge protection parallel
to the relay coil.
Do not short the analog voltage terminals H
and L or the internal power terminals P24 and
all CM's to prevent any VFD damage
When connecting a thermistor to the TH and
all CM's terminals, twist the thermistor cables
and separate them from the rest. Limit the
connection wires to 65 feet.
Control cables
(RXP-RXN, 1~8, H,O,OI etc.)
32
Power cables
(R,S,T,P,N,U,V,W)
Right angle
(90 degrees)
10cm or more