Adtech iMASTER – A1 Series User Manual page 104

Table of Contents

Advertisement

A1-User's Manual
11.12
AI2 (OI) forced value
Range: 0.00 ~ 100.0 % in 0.01 %
Initial value: 0.00 %
Allows the data value of a forced analog input to be changed from 0.0 to 100.0
It is only possible to forced an input that has been selected in parameter
'11.01' (AI forced selection)
11.13
AI2 (OI) filter time
Range: 0 ~ 30000 ms in 1 ms
Initial value: 100 ms
Defines the filter time constant for analog input AI2 (OI)
The filter time is that VFD is realized 63% of 100%
100
63
11.14
AI2 (OI) source min
Range: 0.00 ~ 100.0 % in 0.01 %
Initial value: 0.0 %
Defines the minimum site value for analog input AI2 (OI)
Set the value actually sent to the drive when the analog signal from plant is wound to its
minimum setting.
11.17 (AI2 scaled at AI2 max)
11.16(AI2 scaled at AI2 min)
%
Unfiltered signal
Filtered signal
T
T: Filter time constant
11.11 (AI2 scaled value)
11.14 (AI2 source min)
t
11.10 (AI2 actual value)
11.15 (AI2 source max)
100