A1-User's Manual
40.13
Pre PID frequency
0: Disable Pre PID function
Range: 0.00 ~ 400.0 Hz in 0.01 Hz
Initial value: 0.00 Hz
Program the frequency reference when PID function is activated. Once the VFD frequency
out reaches this value in
VFD is operated in closed loop control.
01.01 (Output Frequency)
40.17 (PID feedback)
40.14
PID sleep frequency
Range: 0.00 ~ 400.0 Hz in 0.01 Hz
Initial value: 0.00 Hz
Program the frequency reference when the VFD goes sleep
01.01 (Output Frequency)
40.18 (PID output)
40.15
PID sleep/wake delay time
Range: 0.0 ~ 30.0 Sec in 0.1 Sec
Initial value: 0.0 Sec
Program the frequency reference when the VFD goes sleep
'40.13' (Pre PID frequency)
Run command
40.02 (PID reference)
PID operation
Run command
Run
Motor status
PID control function is enabled and the
ON
40.13 (Pre PID frequency)
ON
ON
40.14 (PID Sleep reference)
40.15 (Sleep/Wake up
Delay time)
40.16 (PID Wake Up frequency)
Stop
Run
149