Adtech iMASTER – A1 Series User Manual page 182

Table of Contents

Advertisement

A1-User's Manual
Name
Input Phase Loss
Ground Fault
Fan Fault
OVS control fail
External Event
Safety input trip
System Overload
Detection Fault
System Underload
Detection Fault
Braking Resistor
Overload Trip
Day of use Limited
Trip
Cause(s)
A function that detects phase loss in the input AC source. Detection is
performed using the fluctuation in the main circuit's DC voltage. Also, in
the case of degradation of main capacitors it could be occurred.
When ground fault is detected on running condition, the output is cut
off.
The Fan fault is indicated when the fan is not rotated
The OVS output frequency is higher than maximum OVS output
frequency during the setting time when the OVS function is enabled
When the external equipment or unit has an error, the VFD receives the
corresponding signal and cuts off the output.
When the terminal of safety has opened
The output current of the drive is greater than the detection level set for
this feature when it enabled
The output current of the drive is less than the detection level set for this
feature when it enabled
When DBR exceeds the duty cycle of the braking resistor this fault will
occur. The circuit is designed to calculate and protect the braking
resistor from thermally overheating
Day of use Limited Trip
178
Error
Code
PF
GF
FF
ovSF
EE1~EE5
SAFE
oLdt
uLdt
brot
dL