A1-User's Manual
3) Use Environment & Option
Feature
Ambient Temperature
Storage temperature
Ambient humidity
Vibration
Shock
Location
Standard Compliant
Protective Design
Option
'98.01'(Motor control mode)
Note 1)
Set a value more than 2kHz at
Sensorless vector performance will be reduced when using a motor less than
half of the rated capacity of the VFD.
Multiple motors cannot be driven by sensorless vector control.
Note 2) To operate the motor over rated frequency, consult the motor manufacturer about
the maximum allowable rotation speed.
CT (Heavy Duty) load: - 10 ~ 50℃
VT (Normal Duty) load: - 10~ 40℃
(It is recommended that you use less than 80% load when you use VT load at 50℃.
And if ambient temperature is above 40℃, Carrier frequency should be lower than
default value.)
-20~60℃
Below 90% RH (Installed with no dew condensation)
5.9m/s
(0.6G). 10~55Hz
2
10 Hz to 20Hz, 9.8m/s² Max, 20Hz to 55Hz, 5.9m/s² Max
Under 1000m above sea level, indoors
(Installed away from corrosive gasses dust)
UL 508C, IEC 61800-3
IP00 open-chassis, NEMA Type 1 enclosure.
Fieldbus, Ext I/O, Encoder, Remote operator, Bracket, AC reactor,
Noise filter, Braking resistor, Dynamic braking unit
(EMC filter and DC reactor are Built in.)
to 2 (sensorless vector control) Selected, refer to below
'98.03'(PWM carrier frequency)
Performance Specification