Motor data selection
0: Standard motor data ----- Initial value
1: Auto tuning data
Program to select between standard motor data and auto tuned data
99.10
Motor resistance R1
Range: 0.1 ~ 30.0 Ohm in 0.001 Ohm
Initial value: depend on VFD models
The initial value is Hyundai motor data
99.11
Transient inductance
Range: 0.01 ~ 100.0 mH in 0.01 mH
Initial value: depend on VFD models
The initial value is Hyundai motor data
99.12
Motor resistance R1 (Auto tuned data)
Range: 0.1 ~ 30.0 Ohm in 0.001 Ohm
Initial value: depend on VFD models
Value determined during auto tuning process
99.13
Transient inductance (Auto tuned data)
Range: 0.01 ~ 100.0 mH in 0.01 mH
Initial value: depend on VFD models
Value determined during auto tuning process