Adtech iMASTER – A1 Series User Manual page 144

Table of Contents

Advertisement

A1-User's Manual
31.10
Automatic reset item 1
Range: 0x00 ~0xFF
Initial value: 0x00
Selects faults that are automatically reset the parameter is a 16-bit word with each bit
corresponding to a fault type. Whenever a bit is set to 1, the corresponding fault is
automatically reset. The bits of this binary number correspond to the following faults
15
14
EE 5
EE 4
31.11
Automatic reset item 2
See the parameter '31.10' (Automatic reset item 1)
31.12
User reset item selection
Range: 0~32
Initial value: 0
Defines the fault that can be automatically reset using parameter '31.10' (Automatic reset
item 1) or '31.10' (Automatic reset item 1),
31.13
Restart trial 1
Range: 0 ~10 in 1
Initial value: 0
Defines the number of automatic fault resets at
31.14
Restart trial 2
Range: 0 ~10 in 1
Initial value: 0
13
12
11
EE 3
EE 2
EE 1
Value
Type of Trip
0
-
1
oC (Over Current)
2
ov (Over Voltage)
3
Lv (low Voltage)
4
Sc (Short circuit)
5
-
6
ot (Over Temperature)
7
EtH(Motor Over Load)
8
EE1 (External Emergency 1)
9
E2PE (EEPROM Error)
10
CE (Communication Error)
11
-
12
GF (Ground Fault)
13
-
14
Iolt (VFD Over Load)
15
PF (Input Phase Loss Fault)
10
9
8
7
6
User
-
-
-
-
bit 10
Value
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
'31.10' (Automatic reset item 1)
140
5
4
3
2
1
-
-
Sc
Lv
ov
Type of Trip
-
SAFE (Safety Fault)
-
ovSF (OVS Fail)
-
-
EE2 (External Emergency 2)
EE3 (External Emergency 3)
EE4 (External Emergency 4)
EE5 (External Emergency 5)
-
FF (Fan Fault)
Profibus-DP Trip
Device-Net trip
System OL trip
System UL trip
Day of use Limited Trip
0
oC

Advertisement

Table of Contents
loading

Table of Contents